General specifications
Product name
Eaton Moeller® series DILL lamp load contactor
Part no.
DILL12(24V50HZ)
EAN
4015081041787
Product Length/Depth
97 millimetre
Product height
85 millimetre
Product width
45 millimetre
Product weight
0.426 kilogram
Certifications
CE
UL 60947-4-1
VDE 0660
CSA
CSA File No.: 012528
CSA Class No.: 3211-04
UL
IEC/EN 60947
UL Category Control No.: NLDX
UL File No.: E29096
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
Product Tradename
DILL
Product Type
Lamp load contactor
Product Sub Type
None
General information
Application
Contactors for lighting systems
Connection
Screw terminals
Degree of protection
IP00
Lifespan, electrical
10,000 Operations
Lifespan, mechanical
1,000,000 Operations (AC operated)
Operating frequency
60 mechanical Operations/h (AC operated)
60 electrical Operations/h
Overvoltage category
III
Pollution degree
3
Product category
DILL Lighting contactors
Rated impulse withstand voltage (Uimp)
8000 V AC
Resistance per pole
2.65 mΩ
Utilization category
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage type
AC
Ambient conditions, mechanical
Shock resistance
6.9 g, N/O main contact, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Altitude
Max. 2000 m
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient operating temperature (enclosed) - min
25 °C
Ambient operating temperature (enclosed) - max
40 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
80 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Electro magnetic compatibility
Emitted interference
According to EN 60947-1
Interference immunity
According to EN 60947-1
Electrical rating
Permissible compensation capacity
470 µF
Rated breaking capacity at 380/400 V
170 A
Rated operational current (Ie)
12 A at AC-1, 220 V 230 V
12 A (High-pressure mercury vapor lamps)
12 A (Metal-halide lamps)
7.5 A (Low-pressure sodium lamps)
14 A (Filament bulbs)
12 A (Electronic upstream devices)
12 A (Mercury blended lamps)
14 A at AC-3, 220/230 V
12 A at AC-1, 380 V 400 V
12 A (High-pressure sodium lamps)
20 A (Conventional reactor starter circuit)
20 A (Fluorescent lamp load - duo circuit)
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
12 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
0 A
Rated insulation voltage (Ui)
690 V
Rated making capacity (cos phi to IEC/EN 60947)
238 A
Rated operational power at AC-3, 380/400 V, 50 Hz
0 kW
Rated operational voltage (Ue) at AC - max
690 V
Short-circuit rating
Short-circuit current rating (basic rating)
5 kA, SCCR (UL/CSA)
125 A, max. Fuse, SCCR (UL/CSA)
125 A, max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)
70 A, Class J, max. Fuse, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
22 kA, CB, SCCR (UL/CSA)
32 A, max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)
70 A, Class J, max. Fuse, SCCR (UL/CSA)
22 kA, CB, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
32 A, max. CB, SCCR (UL/CSA)
Short-circuit protection rating (type 2 coordination) at 400 V
63 A gG/gL
Conventional thermal current Ith
Conventional thermal current ith at 60°C (3-pole, open)
24 A
Switching capacity
Switching capacity (main contacts, general use)
24 A, Maximum motor rating (UL/CSA)
Magnet system
Drop-out voltage
AC operated: 0.6 - 0.3 x UC, AC operated
Duty factor
100 %
Pick-up voltage
0.7 - 1.15 V AC x Us
0.8 - 1.1 V AC x Uc
0.7 - 1.15 V DC x Us
Power consumption, pick-up, 50 Hz
52 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, pick-up, 60 Hz
67 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Power consumption, sealing, 50 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
7.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing, 60 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
Rated control supply voltage (Us) at AC, 50 Hz - max
24 V
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Switching time (AC operated, make contacts, closing delay) - min
16 ms
Switching time (AC operated, make contacts, closing delay) - max
22 ms
Switching time (AC operated, make contacts, opening delay) - min
8 ms
Switching time (AC operated, make contacts, opening delay) - max
14 ms
Contacts
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Special purpose ratings
Special purpose rating of tungsten incandescent lamps
24 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
24 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Design verification
Equipment heat dissipation, current-dependent Pvid
1.2 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0.4 W
Rated operational current for specified heat dissipation (In)
14 A
Static heat dissipation, non-current-dependent Pvs
2.1 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Power contactor, AC switching (EC000066)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching (ecl@ss13-27-37-10-03 [AAB718020])
Rated control supply voltage AC 50 Hz
24 - 24 V
Rated control supply voltage AC 60 Hz
0 - 0 V
Rated control supply voltage DC
0 - 0 V
Voltage type for actuating
AC
Number of normally closed contacts as main contact
0
Number of normally open contacts as main contact
3
Type of electrical connection of main circuit
Screw connection
Operating voltage AC 50 Hz
230 - 400 V
Operating voltage AC 60 Hz
230 - 400 V
Rated operation current Ie at AC-1, 400 V
12 A
Rated operation current Ie at AC-3, 400 V
0 A
Rated operation power at AC-3, 400 V
0 kW
Rated operation current Ie at AC-4, 400 V
0 A
Rated operation power at AC-4, 400 V
0 kW
Rated operation power NEMA
0 kW
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Modular version
No
Width
45 mm
Height
85 mm
Depth
97 mm