Compact and rugged - for service calls under harsh conditions and laboratory use
The METRISO INTRO fulfills all expectations and requirements for getting
started with the premium class. Thanks to the included functions, it's
especially well-suited for applications involving troubleshooting and inspection
of electrical installations, as well as for use in service and industrial
applications.
The insulation and resistance measuring instruments allow for quick and
effective testing of protective measures in accordance with:
- DIN VDE 0100
- ÖVE-EN 1 (Austria)
- SEV 1000 (Switzerland)
- and regulations specific to other countries as well.
It's capable of executing all required electrical measurements and tests
quickly and safely, in a retraceable fashion.
Insulation measurement per EN 61557-2 / VDE 0413 part 2
Low-resistance measurement per EN 61557-4 / VDE 0413 part 4
Voltage testing and measurement up to 1000 V Measurement category 300 V CAT IV / 600 V CAT III
The insulation measuring instrument is suitable for the following applications:
- Measurement of insulation resistance at voltage-free devices and
equipment, up to 1000 V
- Testing of the resistance of earthing, protective and equipotential
bonding conductors
- Checking of test objects for absence of voltage
- Testing of floor covering electrostatic discharge capability (using
shielded measurement cables) - EN 1081
- No. in Metrological Registry of Russian Federation: 73063-18
Simplifies your measuring tasks:
- Warning for hazardous shock voltages
- Quick test with red LED indicator on the instrument
- Acoustic signal generation in the event of limit value violations
- Measuring voltage: 250, 500 or 1000 V DC
- Measuring range: 10 kΩ ... 10 GΩ
- Low-resistance measurement: 0.01 ... 10 Ω with automatic polarity reversal
- Voltage measurement up to 1000 V AC TRMS / DC
- Electronic fuse for protection of the low-resistance measurement
Type comparison table
|
|
|
|
|
|
METRISO |
XTRA |
TECH |
PRO |
BASE |
INTRO |
Article number |
M550S |
M550P |
M550R |
M550o |
M550N |
Measurements |
|
|
analog |
|
|
PI, DAR Polarization index measurements |
x |
- |
- |
- |
- |
Riso Uvariable =
50 ... 1000 V
(Limit value 1 MΩ) |
x |
- |
- |
- |
- |
Riso URamp =
50 ... 1000 V
Display of breakdown voltage |
x |
- |
- |
- |
- |
Measuring ranges Riso |
10 k ...
...1 TΩ |
10 k ...
200 GΩ |
10 k ...
...1 TΩ |
10 k ...
100 GΩ |
10 k ...
100 GΩ |
Riso U = 50, 100, 250, 500 /
1000 V |
x / x |
x / x |
x / x |
x / - |
(x) / x |
R 10 Ω... 10 kΩ |
x |
x |
- |
x |
x |
RLO 0,01 ... 10
Ω |
x |
x |
x |
x |
- |
U 0 ... 500 /
1000 V |
x / x |
x / x |
x / x |
x / - |
x / - |
Display functions |
|
|
|
|
|
Backlit display |
x |
x |
x |
x |
x |
Limit value LED Limit (green/red)
Additional acoustic signal, limit value per VDE 0100 |
Riso, RLO |
Riso, RLO |
Riso, RLO |
Riso, RLO |
Riso,
- |
LED for dangerous contact voltage (when switched off) |
x |
x |
x |
x |
x |
LCD symbol for external voltage |
x |
x |
x |
x |
x |
Battery level display |
x |
x |
x |
x |
x |
Special functions |
|
|
|
|
|
Data storage in the instrument, 50.000 objects |
x |
- |
- |
- |
- |
Discharge capacitive devices under test |
x |
x |
x |
x |
x |
Safety shutdown (UBatt < 8 V) |
x |
x |
x |
x |
x |
Features |
|
|
|
|
|
Charging socket, RS232 and USB interface |
x |
- |
- |
- |
- |
Measuring categories CAT II 1000V, CAT III 600V |
x |
x |
x |
- |
- |
Measuring category CAT III 600V, CAT IV 300V |
x |
x |
x |
x |
x |
Integrated 10 MΩ test resistor |
x |
x |
x |
x |
- |
DAkkS calibriation certificate in scope of delivery
(W = Proprietary certificate " ) |
x |
x |
(W) |
x |
- |
|